back to overview
Krypton K
Krypton K H2O2
Measuring and control system for Hydrogen Peroxide
Krypton K
- Low maintenance by automatic sensor cleaning
- Pressure-proof up to 6 bar at 20°C
- Higher safety by integrated flow monitoring
description
Ready for use and tested en bloc system to measure and control of Hydrogen Peroxide.applications
Drinking Water / Beverages
Food Industry
Disinfection
Cooling And Boiler Feed Water
particular characteristics
- Inclusive instrument, single rod sensor, PMMA flow assembly (with sampling point, stop cocks for inlet and outlet, flow monitoring and temperature sensor), automatic sensor cleaning ASR and all necessary cables
- Plain text menu guidance
- Password function
- 2 limit values with delay, assigned to alarm relay
- 2 separate PI-controllers
- Dosage check
- Background illuminated two-line LC-Display for measured value and temperature
- Serial interface RS 485
- Scaleable, glavanically isolated 0/4 .. 20 mA output
- Display of relay status and error messages
- Invertible alarm output, permanent or pulse contact
information
The measuring system Krypton K is also available in 117 VAC and 24 VAC - without additional chargetechnical data
measuring parameter |
|
| Hydrogen Peroxide | 0.00 .. 30.00 mg/l H2O2 |
input characteristics
| temperature measuring range | -30 .. +140°C | ||||||||
| flow monitoring | Flow monitor with integrated Pt 100 | ||||||||
| conditions |
|
output characteristics
| output signal | 0/4 .. 20 mA (scaleable, galvanically isolated) | ||||
| load | max. 500 Ohm | ||||
| registration range | adjustable within measuring range | ||||
| serial interface | RS 485 | ||||
|
power supply
| line voltage | 24 / 117 / 230 VAC, +6 / -10 %, 40 .. 60 Hz |
| power consumption | 10 VA |
ambient conditions
| ambient temperature | operation 0 .. +50°C, storage -20 .. +65°C exception sensors 0 .. 30°C |
||
| relative humidity | max. 90% rH at 40°C (non-condensing) | ||
| protection class |
|
controller
| control response | on/off controller (adjustable hysteresis) P/PI controller (pulse-pause, pulse-frequency or continuous output) |
| relays | 2 relays each with potential-free NO contact, max. 250 V, 6 A, 550 VA 1 alarmrelay each with potential-free NO/CO contact, max. 250 V, 6 A, 550 VA |
| onset delay | o .. 200 sec until controller active |
| digital input | controller stop via external contact |
certificates and approvals
| CE-symbol | Declaration of conformity: The product meets the requirements of the harmonized European standards. It thus complies with the legal requirements of the EC directives. The manufacturer confirms successful testing of the product by affixing the CE symbol. |
mechanical construction
| material | board: PVC, assembly: PMMA, cocks: PP/PVC instruments: ABS, sensors: glass |
| dimensions | 700 x 395 mm |
| sampling point | 1/4'' female threat with stop cock |
| water coupling | inlet/ outlet: 1/2'' female threat (with stop cock) tube connection DN 6/8 |
order information
name |
description |
article number |
| Krypton K H2O2 | measuring system (230 V), Hydrogen Peroxide | 70005450K |
accessories
sensors
| PtPt-600-OO-2-1-PG | PtPt-600-OO-2-1-PG is a single rod sensor with integrated counter electrode. This potentiostatic double platinium sensor is suitable for measuring hydrogen peroxide. |
accessories
| PKV 30-DPS | Converter for PROFIBUS-DP for max. 32 instruments of the K 100 oder dialog series. Converting of RS 485 to PROFIBUS-DP interface, instrument in a housing for installation on a top hat trail, dimension 105 X 105 x 80 mm (HxBxT), connectioncable inclusive |
| Pooltester | POOLTESTER is a colorimetric rapid test for easy determination of Hydrogen peroxide concentrations that can be used as an indication measurement for our amperometric measuring systems. Naturally, regarding resolution and accuracy, the rapid test does not come close to the Krypton systems, and it cannot replace a fotometric measurement. However, it provides a quick orientation and can therefore prove helpful during installation or routine comparison. The POOLTESTER comes in a robust plastic casing with 20 tablets in a blister pack and a multi-language manual. |
| S-341 data logger | The bus data logger S-341 on the base of the RS-485 with Kuntze protocol reads, shows, and stores measuring data of up to 10 Kuntze instruments with up to 8 parameters each. |
![]() |
Download datasheetAll information about this product for your reference |
|
Collect and zip downloads
If you want to download several documents, you can collect and download them as one zipped file to save time |
Download collector
There are no files in your download-collector