DeutschEnglish
 Products / Instruments  / pH/ORP 
back to overview

K 100 (W) IL

Measuring and control instrument for the inductive conductivity measurement

K 100 W                K100
K 100 W K100
  • Easy and safe operation by plain text menu guidance
  • Safety by password function
  • Automatic temperature compensation

description

The K 100 (W) IL is a sophisticated single-channel instrument for measuring and control of inductive conductivity. Additionaly temperature measurement of the measuring media is possible. The instrument is available in a panel mounted housing (K100 IL) and in a wall mounted housing (K 100 W IL).

applications

  •  Cooling And Boiler Feed Water
  •  Waste Water Treatment
  •  Drinking Water / Beverages

particular characteristics

  • 2 limit values with delay, assigned to alarm relay
  • 2 separate PI-controllers
  • Dosage check
  • Background illuminated two-line LC-Display for measured value and temperature
  • Serial interface RS 485 optional
  • Scaleable, glavanically isolated 0/4 .. 20 mA output
  • Display of relay status and error messages
  • Invertible alarm output, permanent or pulse contact

technical data

measuring parameter

 

Conductivity (inductive) 0 .. 2.000 mS/cm
  0 .. 20.00 mS/cm
  0 .. 200.0 mS/cm
  0 .. 2000 mS/cm

input characteristics

temperature measuring range -30 .. +140 °C
temperature coefficient Adjustable 0 .. 8,0 %/°C or non-linear

output characteristics

output signal 0/4 .. 20 mA (scaleable, galvanically isolated)
load max. 500 Ohm
registration range free scaleable within the measuring range
serial interface RS 485 (optional)
 
Baud rate 9600
data format 8 bit


power supply

line voltage 24 / 117/ 230 VAC, +6/-10%, 40 .. 60 Hz
power consumption 10 VA

ambient conditions

ambient temperature Operation 0 .. +50 °C, storage -20 .. +65°C
relative humidity max. 90% rH at 40°C (non-condensing)
protection class
panel mounted housing IP 54 (front), IP 30 (housing)
wall mounted housing IP 65


controller

control response on/off controller (adjustable hysteresis)
P/PI controller (pulse-pause, pulse-frequency or continuous output)
relays 2 relays, each with a potential-free NO contact, max. 250V, 6 A, 550 VA
1 alarmrelay with potential-free CO/NO contact, max. 250V, 6A, 550 VA
onset delay 0 .. 200 sec till controller active
digital input Controller stop via external contact

certificates and approvals

CE-symbol Declaration of conformity: The product meets the requirements of the harmonized European standards. It thus complies with the legal
requirements of the EC directives.
The manufacturer confirms successful testing of the product by affixing the CE symbol.

mechanical construction - panel mounted housing

material Noryl
dimensions 90x90x116 mm
installation dimensions 92x92x140 mm
weight 0.75 kg
connection push-srew terminals

mechanical construction - wall mounted housing

material ABS
dimensions 165x160x85 mm
weight 0.95 kg
connection Spring-loaded terminals

K 100
K 100 K 100 W
K 100 W

order information

name

description

article number

K 100 IL inductive, panel mounted housing, 230 VAC 100190K
K 100 W IL inductive, wall mounted housing, 230 VAC 105190K

accessories

accessories

PKV 30-DPS Converter for PROFIBUS-DP for max. 32 instruments of the K 100 oder dialog series. Converting of RS 485 to PROFIBUS-DP interface, instrument in a housing for installation on a top hat trail, dimension 105 X 105 x 80 mm (HxBxT), connectioncable inclusive
S-341 data logger The bus data logger S-341 on the base of the RS-485 with Kuntze protocol reads, shows, and stores measuring data of up to 10 Kuntze instruments with up to 8 parameters each.

Download datasheet

All information about this product for your reference

Collect and zip downloads

If you want to download several documents, you can collect and download them as one zipped file to save time

Download collector

There are no files in your download-collector

K 100. Purposive meter and controller…
For the purposive measurement and control of a single parameter, the K 100 is the right choice. With temperature measurement and compensation, bidirectional PI controller with alarm function, one analog output and optionally serial interface.

Easy operation…

Text menu. Text messages for status and alarm. Indication of controller relay status. Simple manual operation of the relays.

Value for money…

Analog output, controller with two relays, additional alarm relay, external controller stop, and much more – all inclusive and ready-to-use.

Fits in very well…

Choose between wall-mounting housing with IP65 and panel-mounting housing 96x96mm.

dialog. Versatile meter and controller...
Large graphical display, trend indication, log book, text menu. Two PID controllers, three analog outputs, and serial interface.

Redundance spells security...

Reliable process control. With the dialog´s double measurement function you will immediately recognise sensor faults.

Ratio spells efficiency...

Surveillance of treatment processes. Monitor the efficiency of your ion exchangers via conductivity reduction using the dialog´s difference measurement function.

Combination spells compensation...

Independence of interferences. For disinfection with Chlorine, the pH value plays an important role. With the dialog you can measure and control Chlorine and pH simultaneously, and automatically compensate the pH influence on the Chlorine measurement.