DeutschEnglish
 Products / Instruments  / Chlorine 
back to overview

dialog W 2 CL2/PR R

Double-channel measuring and control instrument for free chlorine and pH-Value - additionaly ORP optional

dialog W 2 CL2/PR R (20 mg)
dialog W 2 CL2/PR R (20 mg)
  • Double measurement of free chlorine and pH -optionally with additional ORP measurement
  • Easy and safe operation by plain text menu guidance
  • Log book function
  • Graphical trend display of the last 3 h

description

The dialog W 2 CL2 PR R is a sophisticated instrument for the precise measurement and control of the chlorine concentration and the pH-value - additionally an ORP measurement is optional. It is available in a wall mounted housing.

applications

  •  Drinking Water / Beverages
  •  Waste Water Treatment
  •  Disinfection

particular characteristics

  • Variable assignment of relay and current outputs
  • 2 limit values with delay
  • Dosage check
  • Semi-automatic two point-calibration for pH
  • Slope and zero point monitoring for pH
  • Automatic or manual pH-value compensation for pH
  • Serial interface RS 485
  • 2 or 3 scaleable, galvanically isolated 0/4 .. 20 mA outputs
  • 2 separate PID-controller
  • Real time clock
  • Background illuminated two-line LC-Display
  • Password function

information

Measuring and control instruments of the dialog series are also available for 117 VAC and 24 VDC (only wall mounted housing) - wihtout additional charge.

technical data

measuring parameter

 

free Chlorine 0 .. 4.00 mg/l
  0 .. 20.00 mg/l
pH-value 0 .. 14.00 pH
ORP -1500 .. +1500 mV

input characteristics

accuracy 1 % mg/L Cl2 of range, +/- 0,01 pH, +/- 1 mV
temperature measuring range -30 .. +140°C
temperature coefficient non-linear
conditions
min. flow 10 l/h recommended: 30 l/h
pH-range 6.0 .. 8.0 pH


output characteristics

output signal 3 0/4 .. 20 mA (scaleable, galvanically isolated)
load max. 500 Ohm
registration range Free scaleable within the measuring range
voltage output +/- 6 VDC for impedance converter
serial interface RS 485
 
Baud rate 9600
data format 8 bit


power supply

line voltage 24 / 117 / 230 VAC, +6 / -10 %, 40 .. 60 Hz
optional: 24 VDC
power consumption 10 VA

ambient conditions

ambient temperature operation 0 .. +50°C, storage -20 .. +65°C
relative humidity max. 90% rH at 40°C (non-condensing)
protection class
wall mounted housing IP 65


controller

control response On/off controller (adjustable hysteresis)
P/PI/PID-controller (pulse-pause, pulse-frequency or continous controller output)
relays 3 relays, each with potential-free CO contact, max. 250 V, 6 A, 550 VA
onset delay 0 .. 200 sec till controller active
digital input Controller stop via external contact

certificates and approvals

CE-symbol Declaration of conformity: The product meets the requirements of the harmonized European standards. It thus complies with the legal
requirements of the EC directives.
The manufacturer confirms successful testing of the product by affixing the CE symbol.

mechanical construction - wall mounted housing

material ABS
dimensions 165x160x85 mm
weight 1.25 kg
connection Spring-loaded terminals

dialog W 2 CL2/PR R
dialog W 2 CL2/PR R

order information

name

description

article number

dialog W 2 CL2/ PR R wall mounted housing, 230 VAC, 0 .. 4 mg/l 115212K
dialog W 2 CL2/ PR R 20 mg wall mounted housing, 230 VAC, 0 .. 20 mg/l 115230K

accessories

accessories

CHECKIT Comparator The CHECKIT Comparator is a compact handy colorimeter unit which is suitable for both mobile and static analysis work.
CHECKIT Comparator is a colorimetric rapid test for easy determination of Free Chlorine, Total Chlorine, Chlorine Dioxide or Ozone concentrations that can be used as an indication measurement for our amperometric measuring systems. Naturally, regarding resolution and accuracy, the rapid test does not come close to the Krypton systems, and it cannot replace a fotometric measurement. However, it provides a quick orientation and can therefore prove helpful during installation or routine comparison.
The CHECKIT Comparator comes in a robust plastic casing with all necessary equipment.
PKV 30-DPS Converter for PROFIBUS-DP for max. 32 instruments of the K 100 oder dialog series. Converting of RS 485 to PROFIBUS-DP interface, instrument in a housing for installation on a top hat trail, dimension 105 X 105 x 80 mm (HxBxT), connectioncable inclusive
S-341 data logger The bus data logger S-341 on the base of the RS-485 with Kuntze protocol reads, shows, and stores measuring data of up to 10 Kuntze instruments with up to 8 parameters each.

Download datasheet

All information about this product for your reference

Collect and zip downloads

If you want to download several documents, you can collect and download them as one zipped file to save time

Download collector

There are no files in your download-collector

dialog. Versatile meter and controller...
Large graphical display, trend indication, log book, text menu. Two PID controllers, three analog outputs, and serial interface.

Redundance spells security...

Reliable process control. With the dialog´s double measurement function you will immediately recognise sensor faults.

Ratio spells efficiency...

Surveillance of treatment processes. Monitor the efficiency of your ion exchangers via conductivity reduction using the dialog´s difference measurement function.

Combination spells compensation...

Independence of interferences. For disinfection with Chlorine, the pH value plays an important role. With the dialog you can measure and control Chlorine and pH simultaneously, and automatically compensate the pH influence on the Chlorine measurement.